Interpretation #9080

Published May 29, 2025

Original Request

Code Version
2023
Code
NEC
Code Description
Chapter
2
Section
210.70 (A) (1)
Topic
Required switches at entrances to habitable rooms.

Question

In Residential Construction, is it the intent of the code to require light switches controlling outlets or light fixtures at all entrances to a room.

Answer Published 03/21/2025 at 11:17 AM

No. Please see the attached commentary

Commentary

While we might believe it to be a good idea or if someone has a preference for a listed wall-mounted control device at each entrance, the code language does not require more than one listed wall-mounted control device. More than one is not prohibited nor is it required.