Interpretation #9075

Published February 12, 2025

Original Request

Code Version
2010
Code
BUILDING
Code Description
Chapter
19
Section
1917.1
Topic
Product Approval

Question

Is it correct that a Fl Product Approval is the minimum requirement for the material, fasteners and installation of a tested assembly to meet a specific maximum design wind pressure? And is it correct that a Fl Professional Engineer (P.E.) or Registered Architect (R.A.) can design more stringent or rigid requirements, including fastening, the type of fastener for attachment, that meet standard practices and or certifications such as SDI/ANSI ? And that this is acceptable if approved by the AHJ? This would not change or modify the MDP of the assembly.

Answer Published 02/06/2025 at 7:33 AM

There are three (3) methods available for product approval. The system that has been in place for many editions of the codes is approval by the building official. The building official is authorized in Chapter 1 to approve products based on their suitability, in the opinion of the building official. As most building officials do not consider themselves to be a testing and approval authority, most building officials rely upon one of the next two (2) options. They may accept a report or letter, including a rational analysis from a design professional to base the approval on. This may also include tests and reports from a recognized authority, such as Underwriters Labs (UL), International Code Council Evaluation Services (ICC-ES), Miami-Dade Testing, Texas Department of Insurance (TDI). or others. These options may be used at the discretion of the building official and design professional. The other option is to use the Florida product approval database. If the choice is to use the Florida product approval database, the information that is a part of the approval must be followed. If that information is changed or modified, it then becomes an approval by the building official or a local product approval option. The information contained in the product approval should be followed, allowing for substitutions where so noted on the approval, or the product approval is not applicable.

Commentary

None.