Interpretation #9001

Published February 28, 2025

Original Request

Code Version
2023
Code
EXTBLDG
Code Description
Chapter
Section
810, 1010.1
Topic
Plumbing Fixtures within Alteration Level 2

Question

Chapter 8 section 810 of the Florida Existing Building Code 8th Edition does not explicitly identify when a change in plumbing fixture type or quantity is required under the alteration level 2 classification.

Therefore, is the intent of the Existing Building Code to defer the requirements for plumbing fixtures to section 1010.1 Florida Existing Building Code 8th Edition such that the change in plumbing fixtures to meet current code requirements is only required when the building or space is subject to a change in occupancy?

Answer Published 02/06/2025 at 8:05 AM

Yes, only when there's a change of occupancy as required in Section 1010.1.

Commentary

None