Interpretation #8867

Published March 04, 2025

Original Request

Code Version
2023
Code
BUILDING
Code Description
Chapter
Section
454.2.6.1
Topic
ANSI/APSP/ICC 7 2020 SUCTION ENTRAPMENT PREVENTION

Question

Is it the intend of Section 454.2.6.1 and Chapter 34, Adopted Reference Standards including ANSI/PHTA/ICC 7—2020, containing section 4.4.5.1, to require Building Departments to inspect or obtain information at final inspection of pools that verifies actual maximum possible system flow when a TDH calculation is used to demonstrate at plan review compliance with the safe flow of the Suction Outlet Fitting Assembly?

Answer Published 03/04/2025 at 11:53 AM

Yes

Commentary

None.