Interpretation #8855

Published December 21, 2023

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
25
Section
2510.3
Topic
Lath for cement plaster (stucco)

Question

Is it the intent of 2510.3 and ASTM C1063 to require that lath installed over structural wood sheathing be fastened through the sheathing and to the wall studs?

Answer Published 12/18/2023 at 8:56 AM

Yes, IF the sheathing is nonstructural. ASTM C1063 is a national standard written for open framing or open framing covered with nonstructural sheathing. If the sheathing is structural then the answer is No.

Commentary

For more information, please see the Stucco Institute newsletter - https://stuccoinstitute.com/wp-content/uploads/2020/02/Inspecting-stucco-for-code-compliance-1.pdf