Interpretation #8811

Published August 09, 2023

Original Request

Code Version
2021
Code
RESIDENT
Code Description
Chapter
Section
R303.3
Topic
Bathrooms

Question

Is it the intent of Section R303.3 Exception to require the bathroom exhaust air to be exhausted to the outdoors?

Answer Published 08/09/2023 at 4:23 PM

See also interpretation #8555. The Exception to R303.3, FBC - Residential states the glazed areas (an operable window) shall not be required where artificial light and a local exhaust system are provided. The minimum local exhaust rates shall be determined in accordance with Section M1507. Exhaust air from the space shall be exhausted directly to the outdoors.
The last sentence in the exception clearly states that it shall be exhausted directly to the outdoors. The soffit would not be the outdoors.

Commentary

Outdoor discharge is further explained in Chapter 15 of the Residential volume. M1501.1 Outdoor discharge. The air removed by every mechanical exhaust system shall be discharged to the outdoors in accordance with Section M1506.3. Air shall not be exhausted into an attic, soffit, ridge vent or crawl space.