Interpretation #8807

Published July 19, 2023

Original Request

Code Version
2021
Code
MECHANIC
Code Description
Chapter
Section
602.2.1
Topic
Materials Within Plenums

Question

Can a louvered door on an A/C closet an a/c closet (plenum return) be made out of wood and particle board if it is painted (covered) with intumescent paint

Answer Published 07/19/2023 at 7:46 AM

The use of Intumescent Paint is an alternative to code and should go thru submittal to the building official as a alternative materials, design and methods of construction and equipment, per Section 104.11 FBC

Commentary

As a note, if this is under the Residential volume, it would be exempt from this requirement