Interpretation #8797

Published July 12, 2023

Original Request

Code Version
2021
Code
RESIDENT
Code Description
Chapter
Section
1411.8
Topic
locking freon access ports

Question

Are locking freon access ports required for pool heat pumps?

Answer Published 07/12/2023 at 11:14 AM

Yes, the requirement for the locking caps is for any device that has refrigerant, and that has access ports that are not enclosed in the units cabinet.

Commentary

The chapter heading for chapter 14 is "Heating and Cooling equipment and appliances", 1411.8 is under sub heading as "Heating and cooling equipment", as heat pumps are heating and cooling equipment this section would apply to them as well. Overall purpose of the code section is to restrict access to refrigerant ports.