Interpretation #8764

Published May 06, 2023

Original Request

Code Version
2021
Code
PLUMBING
Code Description
Chapter
Section
403
Topic
Fixture count requirements for 150-seat restaurant

Question

For a Restaurant with 150 fixed seats, is the plumbing fixture count (table 403.1) requirement based on assembly occupants as defined in Sec 403.1.3.1 or is it combined with accessory spaces that have additional occupants by area?

Answer Published 05/06/2023 at 10:33 AM

Per section 403.1 of the Florida Building Code, Plumbing volume, the number of fixtures is based on the TOTAL occupant count determined by the Florida Building Code, Building

Commentary

None.