Interpretation #8762
Published May 11, 2023
Original Request
- Code Version
- 2021
- Code
- ELECTRIC
- Code Description
- Chapter
- Section
- 230.40, exception 2
- Topic
- Quantity of disconnects for an electrical service.
Question
Can a single commercial electrical service consist of separate runs of conductors installed from a utility service transformer to up to 6 service disconnecting means (disconnects not sharing conductors) that are grouped together on a building?
Answer Published 05/11/2023 at 11:24 AM
The answer as posed is yes per NEC 230.2 and 230.40, Exception No. 2. The service conductors would need to be underground and at least 1/0 in size for this exception to apply.
Commentary
None.