Interpretation #8742

Published April 11, 2023

Original Request

Code Version
2021
Code
BUILDING
Code Description
Chapter
Section
915.1
Topic
Carbon Monoxide Protection

Question

Is it the intent of Section 915.1 Exemption 1 to require all existing nursing homes to install carbon monoxide detectors inside or directly outside of each room or area where a fossil fuel-burning heater, engine or appliance is currently installed?

Answer Published 04/11/2023 at 7:25 AM

The FBC-B is not a maintenance code. The FBC-Existing Buildings volume addresses CO alarms for additions. These occupancies would be classified as Residential Board and Care Occupancies by the FFPC, and it does not require CO alarms for existing facilities.

Section 915.1 does not apply to existing buildings.

Commentary

None.