Interpretation #8732

Published February 15, 2023

Original Request

Code Version
2021
Code
RESIDENT
Code Description
Chapter
Section
2804.1
Topic
relief valve

Question

Is it the intent of R2804.1 to require tankless water heaters to have relief valves ?
P2804.1Relief valves required.
Appliances and equipment used for heating water or storing hot water shall be protected by one of the following:

1.A separate pressure-relief valve and a separate temperature-relief valve.

2.A combination pressure-and-temperature relief valve.

Answer Published 02/15/2023 at 8:56 AM

The relief valve requirements of R2804.1 and its corresponding plumbing code section 504.4 are intended to pertain to storage-type water heaters operating above atmospheric pressure. According to the IPC Commentary, this section does not address relief valve requirements for instantaneous (tankless) water heaters. Those requirements can be found in the applicable standards for instantaneous water heaters. Gas-fired instantaneous water heaters are covered by ANSI Z21.10.3, which requires overtemperature protection as part of the burner control system, and overpressure protection by installation of a pressure relief valve (normally provided by the manufacturer). Electric instantaneous water heaters are covered by UL 499, which requires overprotection to be built into the temperature control system, but does not require overpressure protection. Always refer to the manufacturer’s installation instructions.

Commentary

None.