Interpretation #8707
Published December 21, 2022
Original Request
- Code Version
- 2021
- Code
- ELECTRIC
- Code Description
- Chapter
- Section
- 2701
- Topic
- 2017 NEC 300.4(F)
Question
Is it the intent of 2017 NEC 300.4(F) Exception 1 and 352.10(A) to allow the use of Schedule 40 PVC conduit or other raceway to run a branch circuit to a kitchen island such that the conduit is run in a groove formed by tile setting 'mud' and is protected by porcelain or other tile on top?
Answer Published 12/21/2022 at 3:07 PM
Yes, rigid nonmetallic Schedule 40 PVC conduit can be installed under floor tiles in a groove without nail plating per 2017 NEC 300.4(F) Exception 1 which states: "Steel plates...shall not be required to protect...rigid nonmetallic conduit."
Commentary
None.