Interpretation #8707

Published December 21, 2022

Original Request

Code Version
2021
Code
ELECTRIC
Code Description
Chapter
Section
2701
Topic
2017 NEC 300.4(F)

Question

Is it the intent of 2017 NEC 300.4(F) Exception 1 and 352.10(A) to allow the use of Schedule 40 PVC conduit or other raceway to run a branch circuit to a kitchen island such that the conduit is run in a groove formed by tile setting 'mud' and is protected by porcelain or other tile on top?

Answer Published 12/21/2022 at 3:07 PM

Yes, rigid nonmetallic Schedule 40 PVC conduit can be installed under floor tiles in a groove without nail plating per 2017 NEC 300.4(F) Exception 1 which states: "Steel plates...shall not be required to protect...rigid nonmetallic conduit."

Commentary

None.