Interpretation #8659

Published July 11, 2022

Download Final PDF

Original Request

Code Version
2021
Code
MECHANIC
Code Description
Chapter
Section
502.4
Topic
Station Battery Systems

Question

Is it the intent of this section that battery systems do not need ventilation per 502.4.1 and 502.4.2 since it is not regulated per Florida Fire Prevention Code for systems under 100 gallons of electrolyte in a sprinklered building?

Answer Published 07/11/2022 at 7:35 AM

Yes. To conclude no would negate the affect of having the phrase "as regulated by the Florida Fire Prevention Code" in the code. Also see the Code Commentary volume clarifying it is only required for large systems.

Commentary

Please also reference the Florida Fire Prevention Code (FFPC) and NFPA 1 Chapter 52