Interpretation #8611

Published January 24, 2022

Original Request

Code Version
2021
Code
BUILDING
Code Description
Chapter
Section
1507.1.1
Topic
Underlayment

Question

Is it the intent of Section 1507.1.1 that roof slopes that are between 2:12-4:12 that will get asphalt shingles installed are required to have double underlayment even if the underlayment used is a modified bitumen (Peel & Stick)

Answer Published 01/24/2022 at 10:17 AM

FBC-B section 1507.1.1 states: Underlayment for roof slopes 2:12 and greater shall conform to the applicable standards listed in this chapter. 1507.1.1.1 lists 5 means by which underlayment for asphalt shingles may be installed. Method one lists a method which requires only one layer of modified bitumen underlayment.

Commentary

None.