Interpretation #8608

Published January 24, 2022

Original Request

Code Version
2021
Code
BUILDING
Code Description
Chapter
Section
15
Topic
Dune Crossovers

Question

Does section 1015.1 apply to dune crossovers which are constructed to access a beach? Does this section also require that guardrails, stairs, and handrails in these dune crossovers meet the requirements in this chapter even though they are not part of a building means of egress?

Answer Published 01/24/2022 at 10:14 AM

Section 1015.1 is found within Chapter 10 Means of Egress. Means of Egress is defined in Chapter 2 as: A continuous and unobstructed path of vertical and horizontal egress travel from any occupied portion of a building or structure to a public way.
A Structure is defined as: That which is built or constructed. Based on code definitions, a dune crossover is a structure which is constructed, and Chapter 10 requirements for guardrails, stairs, and handrails, unless specifically excepted, are required.

Commentary

None.