Interpretation #8590

Published November 15, 2021

Original Request

Code Version
2021
Code
RESIDENT
Code Description
Chapter
Section
P2503.1
Topic
DWV Testing- Rough Plumbing

Question

Is it the intent of FBC-Residential R2503.1 to allow an underground DWV test on a single story house to serve as the complete required rough plumbing test - eliminating the need for any testing of above-grade piping subsequently installed?

Answer Published 11/15/2021 at 10:26 AM

No, testing only the underground DWV system does not satisfy the requirements of the section P2503.5.1, which calls for a 5 ft. head test above the highest fitting connection. Branch tees and waste arms are usually installed subsequent to the underground plumbing, and it is important that these joints be water tested as well.

Commentary

None.