Interpretation #8532

Published June 08, 2021

Original Request

Code Version
2021
Code
BUILDING
Code Description
Chapter
Section
2406.4.2
Topic
Protection of glazing

Question

Is it the intent of Exception 2 to allow the use of fixtures such as a countertop that is 26" wide by 36" high as a permanent barrier in order to forego the requirement for safety glazing where glazing in an individual operable panel adjacent to a door where the nearest vertical edge of the glazing is within a 24-inch arc of either vertical edge of the door in a closed position and where the bottom exposed edge of the glazing is less than 60 inches above the walking surface?

Answer Published 06/08/2021 at 12:49 PM

The intent was to not have glazing in an area that a human could contact while operating the door. Exception 2 allows for a permanent barrier to fulfill the requirement to distance the human from the glazing. A base cabinet most likely does not meet the barrier requirement.

Commentary

None.