Interpretation #8520

Published April 23, 2021

Download Final PDF

Original Request

Code Version
2021
Code
ENERGY
Code Description
Chapter
Section
R403.13.1
Topic
Ducted Dehumidifiers

Question

Is it the intent of Section R403.13.1, exception 3 to not allow the connection of a dehumidifier to or from the main return duct of a split system?

Answer Published 04/23/2021 at 8:19 AM

Yes. The intent is to not connect the dehumidified warmer air into the return air of a split system.

Commentary

None.