Interpretation #8482

Published December 03, 2020

Original Request

Code Version
2017
Code
EXTBLDG
Code Description
Chapter
Chapter 3 Provisions for all Compliance Methods
Section
302
Topic
replacement windows

Question

Is it the intent of Section 302 of the FBC - Existing Buildings, 6th Edition to permit the omission of water-resistance flashing in framed openings into which the new fenestration is installed where all of the exterior cladding and water-resistance flashing has been removed prior to the new installation?

Answer Published 12/03/2020 at 12:51 PM

That is not the intent of section 302, rather it is a compliment of general provisions for use in application of the Florida Building Code Existing Building. Your question of new fenestration installation would be governed by section 707.4 Florida Building code Existing Buildings.

Commentary

Section 302 gives guidance on use of one of the allowable 3 methods to meet the modifications to an existing building. 302.4 specifically states that like materials shall be permitted for repairs and alterations, provided no unsafe conditions is created. Water intrusion is an unsafe condition. (hazardous to the health and welfare of individuals)