Interpretation #8459

Published October 19, 2020

Original Request

Code Version
2017
Code
PLUMBING
Code Description
Chapter
Chapter 10 Traps, Interceptors and Separators
Section
Section 1003.3.4 Exception
Topic
Minimum and/or maximum size of each chamber of a multi-chamber grease interceptor.

Question

Is it the intent of Section 1003.3.4, Exception, to require each compartment of a multi-compartment interceptor to be between 750 - 1250 gallons? It seems the code and the Health Department rules may conflict

Answer Published 10/19/2020 at 6:40 AM

The correct section is actually 1003.3.5, not 1003.3.4. This section provides sizing criteria and referenced standards for hydromechanical grease interceptors, as well as for fats, oils and greases disposal systems, and automatic grease removal devices. That encompasses the vast majority of today’s grease interceptors.

An exception is provided for grease interceptors that are sized, constructed, and approved in accordance with Rule 64E-6, FAC, and that are located outside the building. These are commonly referred to as gravity grease interceptors. The purpose of this Florida-specific exception was to permit the continued use of traditional concrete interceptor tanks.

Commentary

The sizing and construction of concrete gravity grease interceptors in Florida is governed by the Health Department. The interpreting Health Department requirements are outside the purview of this committee and the local Health Department and/or serving utility should be consulted for additional guidance.