Interpretation #8432

Published July 29, 2020

Download Final PDF

Original Request

Code Version
2017
Code
BUILDING
Code Description
Chapter
Chapter 4-Special Detailed requirement
Section
403.2.1.2
Topic
Reduction in required fire rating of shafts from 2-hr. rating to 1-hr.

Question

Is it the intent of FBC code Section 403.2.1.2 to allow 1-hr. rated shafts for the entire height of a high-rise building (not greater than 420’ high), thus overriding the code requirements of FBC code Section 713.4 which says that shafts (4) stories or more need to be rated for 2-hrs.?

Answer Published 07/29/2020 at 8:03 AM

Yes, provided the installation meets the sprinkler placement criteria within the shaft and not exceeding past 420 feet in height.

Commentary

None.