Interpretation #8422

Published June 08, 2020

Original Request

Code Version
2017
Code
BUILDING
Code Description
Chapter
Chapter 6-Types of Construction
Section
602.2
Topic
Materials in non-combustible buildings

Question

Is it the intent of this code, which references 603.1, to apply to only the building elements that are within the building envelope? Wouldn’t it also apply to all building elements which are part of the building, including portico/canopy roof structures attached to the building on the exterior?

Answer Published 06/08/2020 at 1:54 PM

Answer to the first question is no. Answer to second question is yes. The items listed are parts of the building whether enclosed with exterior walls or not and must meet the requirements for the type of construction used for the building.

Please see the definitions for additional information about the specific words.

Commentary

None.