Interpretation #8417

Published May 24, 2020

Original Request

Code Version
2017
Code
RESIDENT
Code Description
Chapter
Chapter 27 Plumbing Fixtures
Section
2709.4 Receptor Drains
Topic
Shower Drains for recessed showers

Question

Is it the intent of section 2709.4 to allow a "General Purpose" drain without a flange or weep holes that does not meet approval standards from table 2701.1 to be used in concrete recessed showers that have no liner on the first floor level?

Answer Published 05/24/2020 at 8:31 AM

Yes. See previous BOAF Interpretation #8126. P2709.4 only applies to showers having pans or lining. ASME/ANSI A112.18.2 likewise only references requirements for subdrains for built-up shower pans.

Commentary

None.