Interpretation #8408

Published May 24, 2020

Download Final PDF

Original Request

Code Version
2017
Code
NEC
Code Description
Chapter
Section
Article 514
Topic
Emergency Safety Disconnect (ESD) switch locations

Question

Is it the intent of this section to not allow ESD switches located on a fuel island, which is in the classified area of this fuel island, that is proposed to provide emergency shut off to fuel dispensing devices on an adjacent fuel island that is 100-0" away?

Answer Published 05/24/2020 at 8:18 AM

No. Please see the commentary for additional information

Commentary

The intent of this section is to ensure the Emergency Safety Disconnect (ESD) is located in a visible area from the pumps and within a short enough travel distance so as to be accessible quickly if needed. This section does not allow violating other sections of the code, such as the classified area requirements. Discussion should occur between the designer, owner, contractor and AHJ to ensure the location fits the need and if there are other requirements, such as seal offs due to classified area location, these requirements are met. As with many areas within code, we have general requirements and specific requirements. Safety and functionality mandates we look at all aspects of the requirements, apply the strictest and be sure we are all on the page with understanding the reasons why. In this situation, do not forget to include Fire in the discussions.