Interpretation #8373

Published February 28, 2020

Original Request

Code Version
2017
Code
RESIDENT
Code Description
Chapter
Chapter 3 Building Planning
Section
SECTION R316 FOAM PLASTIC
Topic
Use of DC315 intumescent coating as thermal barrier and garage-residence separation

Question

Is it the intent of Section R316.4 that an approved Thermal Barrier material such as DC315 be used to separate foam plastic insulation from the interior of a garage and also meet the requirements of R302.6 (Dwelling-garage fire separation) when applied to the garage side as listed on Table R302.6?

Answer Published 02/28/2020 at 1:36 PM

No. While the product may be tested as a thermal barrier and an ignition barrier, these barriers are not what is called for in Table R302.6. The ES Report 3702 contains no indication the material may be used as other than a thermal or ignition barrier.

However, Section R302.6 has it's own criteria to meet. The product was not tested for separation.

Commentary

None.