Interpretation #8189

Published October 24, 2018

Original Request

Code Version
2017
Code
EXTBLDG
Code Description
Chapter
Section
706.1 General
Topic
Re-roof requirements

Question

Is it the intent of the Florida Building Code: Existing Building, regarding commercial re-roofing due to hurricane damage and when rooftop HVAC equipment must be removed and reset to allow for the roofing material to be installed, that curb heights be corrected to meet the requirements of FBC: Building, Section 1510.10, as interpreted from 1511.1, 1511.1.1, 1521.4 and 1522.3.2? In the case of total re-roof (more than 25%), does the code compel the contractor to raise mechanical curbs and install hurricane ties?

Answer Published 10/24/2018 at 11:58 AM

Yes…based on the Section cited, the equipment must be placed on code compliant curbs. The issue of “hurricane ties” may be less settled. See comments below:

Section 101.1 of the FBC, EB indicates the provisions of Chapter 1 of the FBC, B also apply. Section 102.8 of the FBC, B volume indicates, “An agency or local government may not require that existing mechanical equipment located on or above the surface of a roof be installed in compliance with the requirements of the Florida Building Code except during reroofing when the equipment is being replaced or moved and is not in compliance with the provisions of the Florida Building Code relating to roof-mounted mechanical units.”

Additionally, Section 706.1.1 of the FBC, EB, 1511.1.1 and 1521.4 of the FBC, B require conformance with the current building code when reroofing. Curb height for HVAC equipment is a minimum of 8” above the roof surface.

Regarding “hurricane ties”, Section 301.15 of the FBC, M, Section 1609.1.1 Exception 8 and the Exception of Section 1620.1 all indicate, “Exposed mechanical equipment or appliances fastened to a roof or installed on the ground in compliance with the code using rated stands, platforms, curbs, slabs, walls, or other means are deemed to comply with the wind resistance requirements of the 2007 Florida Building Code, as amended.”

Commentary

None.