Interpretation #8152

Published August 22, 2018

Original Request

Code Version
2017
Code
ELECTRIC
Code Description
Chapter
Section
E3703.2
Topic
Kitchens

Question

Are the 2 required 20 amp branch circuits required to be installed for a Summer Kitchen built outside usually on a pool deck attached or not attached to the SFR structure.

Answer Published 08/22/2018 at 7:36 AM

Yes, according to NEC 210.11 (C)(1) two or more 20 amp circuits are required for every residential kitchen, not just counter-tops. In addition, NEC 210.52 (B)(3) further states that "no small-appliance branch circuit shall serve more than one kitchen

Commentary

If it meets the definition of a residential kitchen it requires the small-appliance branch circuits. If a portable grill space is provided this would no longer be a kitchen by definition.