Interpretation #8147

Published July 25, 2018

Original Request

Code Version
2017
Code
BUILDING
Code Description
Chapter
Section
1006.3
Topic
Exit stairs in open parking garages

Question

Are open exit stairs allowed in a 7 story open parking garage (not a high rise)?

Answer Published 07/25/2018 at 6:01 PM

FBC-B 1019.3, Item 6 permits exit access stairways and ramps in open parking garages that serve on the parking garage to be open,

Commentary

It is specifically allowed by FBC-B 1019.3 Occupancies other than Groups I-2 and I-3. In other than Group I-2 and I-3 occupancies, floor openings containing exit access stairways or ramps that do not comply with one of the conditions listed in this section shall be enclosed with a shaft enclosure constructed in accordance with Section 713.