Interpretation #8139
Published June 26, 2018
Original Request
- Code Version
- 2017
- Code
- BUILDING
- Code Description
- Chapter
- Section
- 1017
- Topic
- Table 1017.2 Exit Access Travel Distance and Section 1017.2.2 Group F-1 and S-1 Increase
Question
Table 1017.2 for S-1 occupancy in a fully sprinkled building allows for 400 feet of exit access distance. Therefore all fully sprinkled S-1 occupancies are allowed 400 feet of exit access distance without using the conditions shown in Section 1017.2.2 Group F-1 and S-1 increase because Table 1017.2 already allows for 400 feet?
Answer Published 06/26/2018 at 7:28 AM
Yes, you are correct. It appears a coordination issue between the 2 tables was required.
Commentary
None.