Interpretation #8139

Published June 26, 2018

Download Final PDF

Original Request

Code Version
2017
Code
BUILDING
Code Description
Chapter
Section
1017
Topic
Table 1017.2 Exit Access Travel Distance and Section 1017.2.2 Group F-1 and S-1 Increase

Question

Table 1017.2 for S-1 occupancy in a fully sprinkled building allows for 400 feet of exit access distance. Therefore all fully sprinkled S-1 occupancies are allowed 400 feet of exit access distance without using the conditions shown in Section 1017.2.2 Group F-1 and S-1 increase because Table 1017.2 already allows for 400 feet?

Answer Published 06/26/2018 at 7:28 AM

Yes, you are correct. It appears a coordination issue between the 2 tables was required.

Commentary

None.