Interpretation #8122
Published May 07, 2018
Original Request
- Code Version
- 2017
- Code
- RESIDENT
- Code Description
- Chapter
- Section
- 302.3
- Topic
- Separation between duplex lanai's with metal roof covering
Question
Is it the intent of 302.3 to require a 1 hour separation between duplex units within a screen room which has a metal skinned roof and walls of screening which is attached to the main structure at the fascia.
Answer Published 05/07/2018 at 1:01 PM
Assuming that the screen enclosure meets the definition of a "Screen Enclosure", then no, because of Exception #3 to Section 302.3 which exempts "Screen enclosure walls of insect screening with a maximum of 25-percent solid flexible finishes".
Commentary
None.