Interpretation #8113

Published April 24, 2018

Download Final PDF

Original Request

Code Version
2017
Code
MECHANIC
Code Description
Chapter
Section
501.3.1 (2)
Topic
Clothes Dryer Vent Discharge Location

Question

Is it the intent of 501.3.1 (2) that the location of the clothes dryer discharge location be a minimum of 10 feet from an operable opening of a building?

Answer Published 04/24/2018 at 9:21 AM

No. FBC-M 504.4 is specific to clothes dryer exhaust and merely states "Dryer exhaust ducts for clothes dryers shall terminate on the outside of the building and shall be equipped with a backdraft damper". As such as long as the exhaust terminates on the outside of the building, compliance is achieved.

Commentary

Also refer to interpretation #7252