Interpretation #8113
Published April 24, 2018
Original Request
- Code Version
- 2017
- Code
- MECHANIC
- Code Description
- Chapter
- Section
- 501.3.1 (2)
- Topic
- Clothes Dryer Vent Discharge Location
Question
Is it the intent of 501.3.1 (2) that the location of the clothes dryer discharge location be a minimum of 10 feet from an operable opening of a building?
Answer Published 04/24/2018 at 9:21 AM
No. FBC-M 504.4 is specific to clothes dryer exhaust and merely states "Dryer exhaust ducts for clothes dryers shall terminate on the outside of the building and shall be equipped with a backdraft damper". As such as long as the exhaust terminates on the outside of the building, compliance is achieved.
Commentary
Also refer to interpretation #7252