Interpretation #8111

Published April 13, 2018

Original Request

Code Version
2017
Code
ELECTRIC
Code Description
Chapter
Section
517.2
Topic
Health Care facility

Question

Is it the intent of 2014 NEC 517.2 Definition of Health Care facility to include a Holistic Medical Reiki practice that has patient exam rooms?

Answer Published 04/13/2018 at 11:56 AM

Probably not. Please see the attached commentary.

Commentary

According to one source Reiki is defined as "Reiki is a Japanese technique for stress reduction and relaxation that also promotes healing. It is administered by "laying on hands" and is based on the idea that an unseen "life force energy" flows through us and is what causes us to be alive. If one's "life force energy" is low, then we are more likely to get sick or feel stress, and if it is high, we are more capable of being happy and healthy." As such, if no use of equipment, invasive procedures or other medical techniques or used, this area may not qualify as requiring the redundant grounding that is typically a part of the NEC Article 517 requirements. Much like many Chiropractic practices, no invasive procedures are used and virtually no equipment, other than the practitioners hands are a part of the treatment. While the final decision rests with the Building Official, all factors need to be taken into account and a discussion with the applicant may be appropriate.