Interpretation #8109

Published May 07, 2018

Original Request

Code Version
2004
Code
ACCSCODE
Code Description
Chapter
1
Section
106
Topic
Accessible route

Question

Is a terrace or a balcony in a high-rise condominium building considered a "space or element" as defined? Is access to the balcony or terrace part of the accessible route requiring accessible thresholds?

Answer Published 05/07/2018 at 12:41 PM

Yes, there are requirements for the threshold but not the 1/2-inch limit. While the standard requirements for a threshold to a balcony is 3/4", the FBC-A - Fair Housing Accessibility Guidelines specifically address Exterior deck, patio, or balcony surfaces in covered dwelling units. . Since the requester states high-rise, we will assume the balcony is concrete. FHAG Requirement 4 Item (5) will allow a 4-inch difference from the floor level of the interior of the dwelling unit if the balcony or deck floor is of impervious material such as concrete, brick, or flagstone.. . See the commentary attached.

Commentary

While the interior of a private residence may not be required to comply with certain elements of the accessibility guidelines, Fair Housing requirements apply. Fair Housing falls under the Department of Housing and Urban Development (HUD) and has requirements that differ from accessibility in some cases. One of the important distinctions is the allowance for something to made adaptable. The final decision rests with the Building Official and if it is appealed, the appeal would follow a process defined by the guidelines and laws in place at the time.