Interpretation #8101

Published April 03, 2018

Original Request

Code Version
2017
Code
RESIDENT
Code Description
Chapter
Section
R318.7
Topic
Termite Inspection Clearance

Question

Specific to masonry exterior wall applications, is it the intent of FRC to require 6-inch inspection clearance between 2-part stucco veneer and grade? Assuming no exceptions apply...

Answer Published 04/03/2018 at 7:16 AM

The code appears to be very clear on when and where these clearances are required. The code, being a minimum compliance document, does not prohibit larger areas for the inspection and monitoring. While it may be advisable to ensure an inspection area is visible, the code requires the following:
R318.7 Inspection for termites. In order to provide for inspection for termite infestation, clearance between exterior wall coverings and final earth grade on the exterior of a building shall not be less than 6 inches (152 mm).
Exceptions:
1.Paint or decorative cementitious finish less than 5/8 inch (17.1 mm) thick adhered directly to the masonry foundation sidewall.
2.Access or vehicle ramps which rise to the interior finish floor elevation for the width of such ramps only.
3.A 4-inch (102 mm) inspection space above patio and garage slabs and entry areas.
4.If the patio has been soil treated for termites, the finish elevation may match the building interior finish floor elevations on masonry construction only.
5.Masonry veneers constructed in accordance with Section R318.4.

Commentary

None.