Interpretation #8091

Published March 15, 2018

Original Request

Code Version
2017
Code
RESIDENT
Code Description
Chapter
Section
R311.7.5.1
Topic
Risers

Question

For a landing at the bottom of a main entrance staircase leading into a home, may tile or pavers be installed on the surface if that makes the first riser from the landing to the first tread less than 7inches?

Answer Published 03/15/2018 at 7:09 AM

Section: R311.7.5.1 states that "The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch". As long as the end result is within this parameter, the installation would be compliant. Note that the code does not specify a minimum required riser height; the code only limits the maximum riser height and the maximum deviation between riser heights.

Commentary

None.