Interpretation #8088

Published March 15, 2018

Original Request

Code Version
2017
Code
RESIDENT
Code Description
Chapter
Section
Alternative materials, design and methods of construction and equipment.
Topic
"Unless otherwise specified" in Stucco Code referenced Standards (ASTM C926 and C1063)

Question

Does the “unless otherwise specified” in C926 and C1063 allow a designer to specify something in their plans that is less than the equivalent of that prescriptively prescribed in the Code or Code Referenced Standards in quality, strength, effectiveness, fire resistance , durability and safety?

Answer Published 03/15/2018 at 7:01 AM

No, an alternate method or material must be approved by the building official and must be equal to or better than specified in the code or standard.

Commentary

None.