Interpretation #8055

Published January 08, 2018

Original Request

Code Version
2014
Code
RESIDENT
Code Description
Chapter
3
Section
302.1
Topic
Glass-block in an exterior rated wall

Question

Is it the intent of Table R302.1(1) to not allow glass block with a 1 hour rating in a wall built on a zero lot line? If the structures are separated by eight (8) feet would it be acceptable?

Answer Published 01/08/2018 at 11:15 AM

Section R302 of the 5th Edition was revised by statute to allow zero lot line buildings to have openings and non-rated roof overhangs as follows:
7. For zero lot line developments where permitted by local regulations, openings and roof overhang projections shall be permitted on the exterior wall of a building located on a zero lot line when the building exterior wall is separated from an adjacent building exterior wall by a distance of 6 feet or more, and the roof overhang projection is separated from an adjacent building projection by a distance of 4 feet or more, with 1-hour fire-resistive construction on the underside of the overhang required, unless the separation between projections is 6 feet or more.

Therefore, glass block is permitted on the zero lot line side when there is a fire separation distance of 6'0" or more measured building face to building face.

Commentary

None.