Interpretation #8035

Published November 28, 2017

Original Request

Code Version
2014
Code
ENERGY
Code Description
Chapter
4
Section
C402.4.5.2
Topic
Outdoor air intakes and exhausts

Question

Section C402.4.5.2 has exceptions to the use of Class 1A motorized dampers. Exception 1 has subheadings for the exception. Does each subheading, (e.g. 1.4), stand by itself as an individual exception? or should all subheadings be taken together, (e.g. 1.1-1.4)?

Answer Published 11/28/2017 at 10:07 AM

They must be taken as a group. All apply to use the exception.

Commentary

None