Interpretation #8030

Published November 22, 2017

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
1
Section
FBC 107.4
Topic
Amended construction documents

Question

Is it acceptable for changes made during construction that are not in compliance with the approved construction documents to NOT be resubmitted for approval as an amended set of construction documents.

Answer Published 11/22/2017 at 3:11 PM

No

Commentary

Changes made during construction require the submission of amended construction documents for approval as stated in this section.