Interpretation #8010

Published October 10, 2017

Original Request

Code Version
2014
Code
EXTBLDG
Code Description
Chapter
11
Section
1102.2
Topic
Adding area to an existing non compliant building

Question

Is it the intent of 1102.2 to not allow an addition to a building that per FBC 5th edition (2014) exceeds the area for that type of use even when a fire barrier is used to separate fire areas per table 707.3.10

Answer Published 10/10/2017 at 10:01 AM

The code is clear on this issue. See the following - 1102.2 Area limitations. No addition shall increase the area of an existing building beyond that permitted under the applicable provisions of Chapter 5 of the Florida Building Code,

Commentary

The addition would need to be a new building with fire separation, fire wall, as required by the Florida Building Code, Building. Use of the properly rated and designed fire wall would create a new building which would be required to comply with the current requirements.