Interpretation #7995

Published September 19, 2017

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
1
Section
101.4.4
Topic
Manufactured home maintenance

Question

Section 101.4.4, F.B.C., entitled "Property Maintenance" is Reserved. Is it the intent of the Florida Building Code to require a property owner to follow the permitting, plan review and inspection procedures set forth in section 553.79, F.S., prior to performing routine maintenance such as the replacement of window screens, flooring, hardware, fixtures, etc., that does not involve structural, plumbing, electrical or mechanical replacement or repair.

Answer Published 09/19/2017 at 8:31 AM

The key to the answer is what is maintenance and what is repair. replacement of an a/c unit is not maintenance, while replacing the air filter is. Replacing floor carpet or tile is maintenance, while replacing the decking is not and would require a permit. Note that Florida Statutes require permitting and inspection of non warranty work on mobile homes.

Commentary

Permits for renovations and repairs to mobile homes are not required pursuant to the FBC, but are required by Florida Statute Ch. 320.8285 and 320.8232, F.S. See also BOAF Informal Interpretation Report 7968