Interpretation #7994

Published September 19, 2017

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
5
Section
Table R503.2.1.1(1)
Topic
Clips for roof panels

Question

Is it the intention of Table R503.2.1.1(1) related to roof sheathing to require clips at edges where blocking or other means of support are not provided?

Answer Published 09/19/2017 at 8:44 AM

The Table may not require edge clips. Based on the span rating of the sheathing and whether or not edge support is provided, edge clips may be used as a method for edge support. At some spans, edge support is not required, ergo clips are not required.

Commentary

None