Interpretation #7987

Published September 05, 2017

Download Final PDF

Original Request

Code Version
2014
Code
RESIDENT
Code Description
Chapter
3
Section
316
Topic
Foam Insulation

Question

We have a contractor that is proposing to use a spray-applied polyurethane foam plastic insulation. The contractor is not intending to apply an Ignition barrier due to an exception in their Foam Insulation Evaluation Report stating “Entry to the attic or crawl space is only to service utilities, and no storage is permitted”. The insulation company proposes to leave a notice that states “No attic storage permitted” at the attic access.
Would it be a reasonable interpretation by the Building Official that if there is attic storage space available, the homeowner &/or future home owners will use that space for storage, thus requiring the Ignition Barrier/Intumescent Coating?

Answer Published 09/05/2017 at 10:38 AM

Yes, a thermal barrier is required. According to R316.5 posting a sign is not one of the exceptions listed

Commentary

None