Interpretation #7972

Published September 05, 2017

Original Request

Code Version
2014
Code
EXTBLDG
Code Description
Chapter
8
Section
804.2.2 exception 2
Topic
meaning of the term "floor area"

Question

is it the intent of the code that in section 804.2.2 ex 2, the term "floor area" shall refer the ENTIRE area of the floor of the building on which work is being performed?

Answer Published 09/05/2017 at 10:47 AM

The work area does not always mean 100% of the floor area. It means only that area in which changes are being made. There could be other reasons for requiring the installation of fire sprinklers on the floor. The most likely is a change of use, or occupancy classification.

Commentary

None