Interpretation #7966
Published September 05, 2017
Original Request
- Code Version
- 2014
- Code
- PLUMBING
- Code Description
- Chapter
- 6
- Section
- 606.1 #6
- Topic
- Location of full open valves for hotel rooms/
Question
Is it the intent of code section 606.1 #6 to require full open valves at the entrance to each hotel or motel unit if that unit has cooking equipment?
Answer Published 09/05/2017 at 11:11 AM
The intent is to have an individual shutoff for each unit, possibly 2 if both hot and cold are supplied independently.
Commentary
The definitions create some possible confusion with the wording. The intent is clear and also explained in the commentary. typically a branch supply will run the length of the corridor or building and will be tapped for each unit. the supply to each unit should be provided with a shutoff for maintenance purposes within the unit.