Interpretation #7959

Published May 11, 2017

Original Request

Code Version
2014
Code
MECHANIC
Code Description
Chapter
5
Section
505.2
Topic
Domestic Kitchen Exhaust

Question

Is it the intent of Section 505.2 when referring to the “the exhaust air rate” to mean:

• The exhaust air rate of the apartment, greater than 400 cfm or
• The exhaust air rate of the hood fan

Answer Published 05/11/2017 at 10:55 AM

The "exhaust air rate" in this section, means the exhaust rate capability of the hood. An alternate method request can be made to the Building Official with the justifications for review and possible approval.

Commentary

None