Interpretation #7957

Published May 11, 2017

Download Final PDF

Original Request

Code Version
2014
Code
ELECTRIC
Code Description
Chapter
27
Section
NEC 250.24 and 250.142 along with FEBC 808, 701.2 and 702.4
Topic
Extension of New Wiring from an Existing Three Wire Fed Panel - No Separation of Ground and Neutral

Question

Can new branch circuits be extended from an existing three wire fed panel with no separate neutral and grounds?

Answer Published 05/11/2017 at 11:15 AM

The extensions would be allowed per the existing building code. The extension can not tell whether the ground and neutral are tied together at the service or the panel. GFCI and Arc fault breakers will still work if the panel will accept them. If it won't then a new subpanel would need to be installed that would still have a 3 wire feed. What happens in real life if someone needs to add a receptacle is they will do it on their own or have a friend do it in a manner that may not be code compliant or safe when they find out the cost of a panel replacement with new 4 wire feeder and most often a new service.

Commentary

None