Interpretation #7953

Published July 19, 2017

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
15
Section
1503.4.2.1
Topic
Overflow scuppers

Question

When roof drains are primary, do scuppers need to be 2 inches above the finished roof?

Answer Published 07/19/2017 at 12:14 PM

If scuppers are being provided to drain overflow water, yes. If scuppers are the primary drainage, they are required to be placed level with the roof surface in a wall or parapet. As a secondary system, where required, scuppers must be at least 2 inches and not more that 4 inches above the roof. See 1503.4.2.1 of the building code.

Commentary

None