Interpretation #7948

Published August 17, 2017

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
10
Section
1029.1
Topic
Emergency escape and recue openings

Question

Is it the intent of section 1029.1to require emergency escape and recue openings in R-2 occupancies even if the building is equipped throughout with an approved automatic sprinkler system?

Answer Published 08/17/2017 at 12:32 PM

The answer is yes if the dwelling units have only 1 exit or access to 1 exit. The answer is no if the dwelling units have 2 or more exits or access to 2 or more exits. Section 1029.1 states: "In addition to the means of egress required by this chapter, provisions shall be made for emergency escape and rescue openings in Group R-2 occupancies in accordance with Tables 1021.2(1) and 1021.2(2) and Group R-3 occupancies." Footnote a to table 1021.2(2) (STORIES WITH ONE EXIT OR ACCESS TO ONE EXIT FOR OTHER OCCUPANCIES) states: "a. Buildings classified as Group R-2 equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 and provided with emergency escape and rescue openings in accordance with Section 1029."

Commentary

None